NFU-7000

Part No. F12-77000

Description

Nittan’s SPERA NFU-7000 Fire Alarm Control Panel offers modular components to meet a wide variety of applications. Designed for peer-to-peer network communications, the NFU-7000 allows for a maximum of 63 nodes, while providing reliability, flexibility and expandability. The NFU-7000 EV protocol is based on the platform which has demonstrated its dependability in European Land and Global Marine markets.

This panel is supplied with a loop driver card which is capable of supporting 2 addressable loops, of up to 254 addresses per loop and expandable up to 6 loops. Owing to the contribution of networkability and range of addressable detectors and modules, the Panel is suitable for all site applications from small to large complex multi-area systems.



document_download

Features

  • Fire Alarm Control
  • One driver card capable of 2 loops is equipped as standard
  • NFU-7000 has capability of three driver cards storage (max 6 loops)
  • One loop supports 254 addresses which can be wired in Class A (Style 6 or 7) or Class B (Style 4)
  • Use of shielded cable is not required for SLC loops
  • Modular design
  • Four Class A/B (Style Z/Y) Notification Appliance Circuits rated at 1.7 Amps each
  • One Auxiliary power supply, rated at 1.7 Amps for 24 VDC and one resettable 4-wire power supply
  • Large 16 line x 40 character Back-lit LCD Display with user friendly menu
  • Programmable Switch Inputs which allow for multifunctional outputs
  • Four Status Queues with selector switches and LEDs for Alarm, Supervisory, Trouble and Monitor
  • Auxiliary relay contacts for Common Alarm, Common Supervisory and Common Trouble
  • RS-232 port for remote system printer
  • Two Event History Logs comprised of a 1000 alarm history log for alarm related events and a 6000 event history log for all events
  • Supports three configuration files (current, previous and next configuration) with “hot swap” support
  • Supports Conventional Hardwire Adder Modules
  • Built-in One Man Walk Test operation
  • Provides drift compensation for photoelectric smoke detectors
  • Capability to adjust sensitivity levels of intelligent smoke detectors
  • Real time 3D graphical monitoring and control by Nittan’s NFU-Graphic-monitor
  • BACnet support
  • Supports Boolean logic functions
  • Built-in Ethernet port
  • UL listed for Smoke Control
  • Manual Control Function
  • Input Simulation Function
  • Multiple group bypass function with built-in false alarm prevention technology

– Network Node Bypass
– Node Outputs Bypass
– Input Zone Bypass
– Relay Disconnect
– Device/Circuit Bypass

Network Features

  • Up to 63 panels
  • Peer-to-peer network communications
  • Mutual surveillance / 2 way control available
  • Class A (Style 6 or 7) or Class B (Style 4) wiring configuration
  • ARCNET protocol
  • Supports copper and/or fiber optic network cable

Comments are closed.