Surface Mounting Manual Call Point
Part No: F16-82200
Evolution Manual Call Points are available in a choice of STI ‘ReSet’ IP24 (EV-MCP2-SCI-IP24 Indoor Manual Call Point) or IP67 housing (EV-MCP2-SCI-IP67 Outdoor Manual Call Point). Both devices include Short circuit Isolator (-ve Line), which is a perfect solution to provide Isolation protection for a Zone. They are DIL Switch Addressed and, in the case of the EV-MCP2-SCI-IP24, come with both Backbox & RF Wall Plate as standard.
- Fully integrated -ve Line Isolator*
- Easily resettable with dedicated key
- Supplied with Surface and Flush adaptors
- Self resetting when fault clears
*Note:
+ve and -ve isolator styles cannot be mixed on a system.
Not compatible with Advanced MxPro4 (Mx4000) Panel. Please use Non-SCI model.
Contact Nittan Technical Support for more details and information on panel compatibility.
Operating Voltage | 20-38 Vdc |
Operating Current | Quiescent: 200μA Alarm: 2.2mA |
Standard | EN54-11:2001 + A1:2005 EN54-17:2005 / AC:2007 |
Alarm Indication | RED LED |