NMP-NCA – NMP-NCA Notification Appliance Circuit (Class A) Module
Part No. F12-75145
Description
The plug-in NMP-NCA module provides power for and handles communications to the non-addressable notification appliances. It has one notification appliance circuit that can be wired in the class A configuration.
Up to a maximum of 1A can be connected to a single class A circuit. The circuit is supervised for open, short and earth trouble conditions and will report this status back to an Evolution UL NMP fire alarm control panel.
An additional feature that is included in the NMP-NCA module is that it has the ability to be programmed as a 24v auxiliary special application class A output, which can be used to provide power to external equipment.